Knocking through to create an open-plan kitchen, dining and living space is one of the most popular changes people make to their homes. It brings in light, makes a house feel bigger and suits the way many families live.
What’s easy to miss is that some of the walls you’d like to remove are doing a fire safety job. The walls and doors around a staircase often form the escape route from the upper floors. Take them away and a fire in the kitchen or living room can fill the stairs with smoke before anyone upstairs knows about it.
This guide explains what the official guidance in England says about open-plan layouts, how the rules change with the height of your house, and the ways you can keep an open feel without compromising your escape route. It’s general guidance, not a substitute for advice from building control on your specific project.
Why the staircase matters
In most houses there’s only one way down from the bedrooms: the stairs. Fire guidance is built around keeping that route usable for long enough for everyone to get out, or, where that isn’t possible, giving people another way out such as a suitable window.
The guidance in England is Approved Document B (Fire safety), Volume 1: Dwellings. How much protection it expects depends largely on whether any floor of your house is more than 4.5m above ground level. As a rough guide, that’s the difference between a typical two-storey house and a house with a third storey, including one created by a loft conversion.
Two-storey houses (no floor above 4.5m)
In a typical two-storey house, the guidance relies mainly on early warning and escape windows rather than a fire-protected stair.
On the ground floor, every habitable room (excluding kitchens) should either open directly onto a hall leading to a final exit, such as the front door, or have an emergency escape window or door.
On the first floor, where there’s only one stair, every habitable room (excluding kitchens) should have either an emergency escape window or external door, or direct access to a protected stairway.
An emergency escape window should have an unobstructed openable area of at least 0.33m², be at least 450mm high and 450mm wide, and have the bottom of the openable area no more than 1,100mm above the floor. It should also stay open without being held.
So if you open up the ground floor and the living room no longer opens onto a hall, that room will usually need an escape window or door, and upstairs rooms will need suitable escape windows. Welsh Government guidance on internal walls makes a similar point: in two-storey houses, removing a wall can normally be compensated for with mains-powered interlinked smoke alarms and escape windows, but in houses of three or more storeys that may not be enough.
Smoke alarms
Approved Document B recommends that all dwellings have a fire detection and alarm system to at least Grade D2 Category LD3 under BS 5839-6. In plain terms, that means mains-powered smoke alarms with a standby power supply, such as a battery, covering the escape routes. If you’re creating an open-plan space, building control may look closely at where alarms are positioned and whether they’re interlinked.
Inner rooms
An inner room is a room you can only leave by passing through another room. Open-plan remodelling can create them without anyone noticing, for example a study or snug that’s now reached through the open-plan kitchen-living area. The guidance only allows certain inner rooms, including kitchens, utility rooms, bathrooms and any room on a storey no more than 4.5m above ground that has an emergency escape window.
Three-storey houses (one floor above 4.5m)
Once a house has a storey more than 4.5m above ground, the guidance asks for more. The house should have either:
- a protected stairway, separated from the rest of the house by fire-resisting construction (minimum REI 30) on every storey, leading to a final exit, or to two ground-floor final exits separated from each other by fire-resisting construction and fire doorsets (minimum E 20), or
- an alternative escape route, where the top storey is separated from the lower storeys by fire-resisting construction (minimum REI 30) and has its own escape route to its own final exit.
This is where open-plan plans often run into trouble. If the stairs come down into an open kitchen-living space, the stair is no longer protected all the way to the front door, and the escape route from the top floor passes through the room where a fire is most likely to start.
Doors onto a protected stairway in a house need a minimum fire rating of E 20, often described as FD20. Many people fit FD30 doors because they’re widely available and exceed that minimum. Our guide to FD30 door requirements explains the ratings and where they apply.
Loft conversions and open-plan ground floors
Loft conversions are where most homeowners meet these rules, because the conversion turns a two-storey house into one with a storey above 4.5m. The guidance says the full extent of the escape route should be addressed, with fire-resisting doors (minimum E 20) and partitions (minimum REI 30), upgrading existing doors where needed. Where the layout is open plan, it says new partitions should be provided to enclose the escape route.
There is an alternative approach in the guidance for open-plan layouts. It involves all of the following:
- Sprinkler protection to the open-plan areas.
- A fire-resisting partition (minimum REI 30) and door (minimum E 20) separating the ground storey from the upper storeys. The door should allow people in the loft room to reach a first-floor escape window.
- Cooking facilities separated from the open-plan area by fire-resisting construction (minimum REI 30).
That last point surprises a lot of people: under this route, an open-plan kitchen isn’t simply part of the living space. Agree the approach with building control before work starts. Our guide to pocket doors for loft conversions looks at doors on the new floor.
Taller houses
For houses with two or more storeys more than 4.5m above ground, the guidance adds further measures: either an alternative escape route from each storey more than 7.5m above ground, with extra separation in the stair, or a sprinkler system throughout the house to BS 9251. Projects like this normally need a designer who’s familiar with fire safety from the outset.
Do you need approval to knock through?
Planning Portal guidance says removing a non-load-bearing wall is unlikely to need building control approval, provided it doesn’t affect fire escape routes, ventilation, drainage or electrics. Removing a load-bearing wall does need approval and a structural engineer’s input.
Local building control teams make the fire point directly. Building Control Partnership, a local authority building control service in Hampshire, says any alteration to the walls around a staircase requires building regulations consent, and gives the example of removing a wall that would expose the staircase to an open-plan kitchen. If you’re not sure what a wall does, ask before it comes down.
The guidance in Approved Document B isn’t the only way to comply. A fire-engineered design can sometimes justify a more open layout, but it has to be agreed with building control. Wales, Scotland and Northern Ireland have their own building regulations and guidance.
Keeping an open feel safely
You don’t have to choose between a dark, boxed-in hallway and an unsafe layout. Some practical options:
Glazed fire doors and screens
A fire door with fire-resisting glass lets light through to the hallway while keeping the stair enclosed. Fire-rated glazed screens can do the same for a whole wall. The glass, beads and frame all have to be part of the tested specification. Our glazed fire doors guide explains what to check.
Fire-rated pocket doors
Where a hinged door would get in the way, a tested FD30 pocket door system can let you close off the kitchen or living room from the hall when needed and leave the opening clear the rest of the time. These are complete tested systems, not a standard pocket kit with a fire door hung in it. See FD30 pocket doors explained.
Concealed fire doors
If you want the stair enclosure to feel like part of a clean, minimal wall rather than a row of doors, an FD30 concealed door set sits flush with the wall. Our guide to FD30 concealed doors covers how they work.
Broken-plan layouts
Many designers now enclose the stair and hall but open up the rooms off them, so the kitchen, dining and living areas flow into each other while the escape route stays protected. Because the escape route isn’t changed, it’s usually a more straightforward conversation with building control.
Frequently asked questions
Can I have an open-plan layout in a three-storey house?
Possibly, but not by simply removing the walls around the stair. The guidance expects a protected stairway or an alternative escape route, and for loft conversions it describes an open-plan option involving sprinklers, a fire-resisting partition and door, and a separated kitchen. Agree the design with building control first.
Do I need fire doors in a two-storey house?
Usually not on the stairs, provided upstairs habitable rooms have suitable escape windows and the ground floor rooms either open onto a hall or have an escape window or door. The door between the house and an integral garage is the main exception, which needs an FD30S door with a self-closer.
Does an open-plan kitchen need to be separated?
In a two-storey house, kitchens are excluded from the escape rules for habitable rooms, so an open kitchen is often fine. Under the open-plan option for loft conversions, though, cooking facilities should be separated from the open-plan area by fire-resisting construction.
Do fire doors inside a house need self-closers?
Approved Document B exempts fire doors within dwellinghouses from its self-closer recommendation. The door between a house and an integral garage is not exempt.
Do I need building regulations approval to remove a wall by the stairs?
If the wall is load-bearing or forms part of the fire escape route, yes. Building control teams advise that alterations to walls around a staircase need consent, so check before starting work.