That small blue “Fire door keep shut” sign is one of the most familiar bits of fire safety in any building. It’s also one of the most misunderstood. Some people stick one on every fire door they own, including the door between the kitchen and the hall at home. Others manage a block of flats and aren’t sure whether the communal doors need one on both faces.
This guide explains what fire door signs are for, the three standard wordings, which doors need them, which don’t, and how to fit them sensibly. It’s a practical summary for England, not legal advice. Your fire risk assessment and building control body always have the final say.
Why fire doors carry signs
A fire door only works when it’s shut. Propped open with a wedge or a fire extinguisher, it’s just a heavy door, and smoke can pass straight through it into a corridor or stairwell people need to escape through.
The sign is a reminder aimed at everyone who uses the door, including visitors, contractors and new tenants who don’t know the building. It tells them this door has a job to do and needs to be left closed (or kept clear, if it’s held open automatically).
Signs don’t make a door fire-resisting, of course. The leaf, frame, hinges, seals, closer and gaps all need to be right too. Our guide on how to check a fire door covers those checks.
The three standard fire door signs
Approved Document B (Fire safety), the guidance that supports the Building Regulations in England, sets out three wordings in Appendix C. It says fire doorsets should be marked, as appropriate, with:
- “Fire door keep shut” – for doors that should be kept closed when not in use. This is the one you’ll see most, on corridor, stairwell and lobby doors.
- “Fire door keep locked shut” – for doors that should be kept locked when not in use, such as doors to stores, risers and service cupboards.
- “Automatic fire door keep clear” – for doors held open by an automatic release mechanism or a free-swing device, which close when the fire alarm sounds.
Approved Document B refers to signs complying with BS 5499-5. In practice, buy signs from a reputable safety sign supplier that states which standard they meet.
What the colours mean
“Fire door keep shut” and “Fire door keep locked shut” are mandatory signs, which is why they’re blue. Under the Health and Safety (Safety Signs and Signals) Regulations 1996, mandatory signs are round, with a white symbol on a blue background. Don’t confuse these with the green running-man signs, which mark escape routes and fire exits. A door can be both a fire door and a fire exit and carry both signs, but they mean different things.
Match the sign to how the door works
Getting the wording right matters. If a door is held open on an automatic release linked to the alarm, a “keep shut” sign is misleading. Someone might wedge it shut, or report the open door as a fault. Equally, “keep locked shut” should never go on a door people need to escape through. Fire exits must be easy to open in an emergency.
Which doors need fire door signs?
Approved Document B says that, apart from a short list of exceptions, all fire doorsets should be marked with one of the three signs. In a typical non-domestic or mixed-use building, that includes:
- doors on protected stairways and corridors
- cross-corridor doors that split long corridors into sections
- doors to lobbies
- communal doors in blocks of flats, such as stair and corridor doors
- doors to plant rooms, stores and service risers (usually “keep locked shut”)
Both sides, or just one?
Approved Document B says fire doorsets should be marked on both sides. The exception is fire doors to cupboards and service ducts, which only need marking on the outside, because nobody normally stands on the other side.
A missing sign on the second face is a common finding on inspections, so it’s worth walking round and checking both faces of every door.
Which fire doors don’t need signs?
This is where many people over-sign. Approved Document B lists three groups of fire doorsets that don’t need to follow the signage guidance:
- Doors to and within flats and dwellinghouses. That includes a flat’s own entrance door and fire doors inside a house, such as the door from an integral garage or doors onto the stair in a three-storey home.
- Bedroom doors in “residential (other)” buildings, such as hotel bedroom doors.
- Lift entrance and landing doors.
So if you’ve fitted FD30 fire doors in your own house, you don’t need to put “Fire door keep shut” signs on them. The doors still need to be the right rating and properly fitted. Our guide to FD30 door requirements explains where fire doors are needed in homes.
What about HMOs and shared houses?
Houses in multiple occupation are a grey area, because what’s expected depends on the property type, your council’s standards and your fire risk assessment. Some councils and assessors will want signs on fire doors in the shared parts. Check your licence conditions and fire risk assessment. Our guide to fire doors in HMOs covers the wider rules.
Who is responsible for fire door signs?
In buildings covered by the Regulatory Reform (Fire Safety) Order 2005, such as workplaces and the common parts of blocks of flats, the “responsible person” must carry out a fire risk assessment and keep fire precautions in good order. That includes making sure the right signs are in place and readable. The person is usually the employer, owner, landlord or managing agent.
In blocks of flats, the Fire Safety (England) Regulations 2022 add specific duties. In any building with two or more sets of domestic premises and common parts residents would escape through, the responsible person must tell residents that:
- fire doors should be kept shut when not in use
- residents and their guests shouldn’t tamper with self-closing devices
- faults or damage to doors should be reported to the responsible person straight away
That information has to go to new residents as soon as reasonably practicable and to all residents at least every 12 months. In buildings above 11 metres, there are also routine checks: communal fire doors at least every three months, and best endeavours to check flat entrance doors at least every 12 months.
Signs on communal doors don’t replace that information, but they reinforce it every day.
Where to fit fire door signs
There’s no fixed mounting height set in law. The aim is for the sign to be seen easily by someone walking up to the door. A few practical tips:
- Fit signs at about eye level, roughly in the middle of the leaf’s width, where they won’t be hidden by a push plate, kick plate or vision panel.
- On a pair of doors, it’s common to mark each leaf on both faces, so the sign is visible whichever leaf people use. Your fire risk assessment can confirm what’s needed.
- For “Automatic fire door keep clear”, place the sign so it can be seen when the door is held open, as that’s how people will normally see it.
- Keep signs clean and readable. Replace faded, painted-over or damaged signs. If you redecorate, mask signs or take them off and refit them afterwards.
Self-adhesive or screw-fixed?
Most fire door signs are self-adhesive vinyl or rigid plastic with an adhesive back. Adhesive fixing avoids drilling extra holes in a certified leaf, which is a sensible default. If you do use screws, keep them short, keep clear of the leaf edges, glazing and intumescent seals, and follow the door manufacturer’s guidance. Our article can you cut a fire door? explains why changes to a fire door leaf need care.
If you’re repainting, our guide on painting a fire door covers what to avoid near the seals.
Common fire door sign mistakes
- Sign on one face only. Most doors need marking on both sides.
- The wrong wording. “Keep shut” on a held-open door, or “keep locked shut” on an escape door.
- Signs on doors that aren’t fire doors. A sign doesn’t make a door fire-rated, and it can give a false sense of security.
- Signs on every door at home. Doors within houses and flats are exempt, so you don’t need them.
- Signs covered up. Coat hooks, notices and posters stuck over a sign defeat the point.
- No sign on a new door. When fire doors are replaced in communal areas, it’s easy to forget to put the signs back.
Signs work alongside hardware. A “keep shut” sign means little if the closer doesn’t pull the door fully shut. Our fire door ironmongery guide covers closers, hinges and locks.
Frequently asked questions
Do fire doors in my house need “Fire door keep shut” signs?
No. Approved Document B says doors to and within dwellinghouses and flats don’t need to follow its fire door signage guidance. The doors still need to be the right rating and fitted properly where they’re required.
Does a flat entrance door need a fire door sign?
Not under Approved Document B, which excludes doors to and within flats. The communal fire doors in the corridors and stairs of the block normally do need signs. Check the building’s fire risk assessment.
Do fire door signs need to go on both sides?
Generally, yes. Approved Document B says fire doorsets should be marked on both sides, except doors to cupboards and service ducts, which only need marking on the outside.
What height should a fire door sign be?
The law doesn’t set a height. Fit it at about eye level, where people approaching the door will see it, and where it won’t be hidden by a push plate, vision panel or the door being open.
What’s the difference between “keep shut” and “keep locked shut”?
“Fire door keep shut” is for doors in regular use that must be closed behind you. “Fire door keep locked shut” is for doors to spaces that aren’t normally occupied, like stores and risers, which should be closed and locked when nobody is inside.
Choosing the right fire doors
Signs are the finishing touch. The door itself does the real work. If you’re replacing doors in a home, a rental or a communal area, browse our fire doors range, and read our guide to FD30 vs FD60 fire doors if you’re not sure which rating you need. If you have a question about a specific door, get in touch and we’ll help you find the right one.